Thermocouple Wire Color Code Chart
Two insulated conductor colors can point to different thermocouple types under different standards. Under the common U.S. ANSI/ASTM convention, Type K is yellow positive and red negative, Type J is white positive and red negative, and Type T is blue positive and red negative. Under IEC 60584-3, the common extension cable pairs are green and white for K, black and white for J, and brown and white for T. The first color in each pair is the positive conductor.
Start with the cable marking and equipment documentation, then check the individual conductors against the corresponding table. The cable jacket can provide a clue, especially on an extension cable, but its color should be interpreted separately from the colors of the two legs.
U.S. ANSI/ASTM chart · IEC chart · Identify a wire pair
U.S. ANSI/ASTM thermocouple wiring colors
| Type | Positive (+) | Negative (−) | Extension jacket |
|---|---|---|---|
| J | White | Red | Black |
| K | Yellow | Red | Yellow |
| T | Blue | Red | Blue |
| E | Purple | Red | Purple |
| N | Orange | Red | Orange |
This table shows the common U.S. conductor colors and extension jacket colors for the listed types. A thermocouple-grade assembly can have a different outer jacket from an extension cable of the same type. For example, brown may appear as the outer jacket on thermocouple-grade construction, even when the two internal wires follow their usual type-specific identification. Use the wire designation printed on the jacket or its traceable documentation to settle the grade. The charts and published application data come from OMEGA Engineering’s thermocouple reference and TE Connectivity’s thermocouple type comparison.
IEC thermocouple extension and compensating cable colors
| Type | Positive (+) | Negative (−) | Standard jacket |
|---|---|---|---|
| J | Black | White | Black |
| K | Green | White | Green |
| T | Brown | White | Brown |
| E | Violet | White | Violet |
| N | Pink | White | Pink |
IEC 60584-3 specifies identification and manufacturing tolerances for the extension and compensating cables it covers. The ordinary jacket colors shown above are separate from special markings, including intrinsically safe cable identification. Mineral-insulated extension and compensating cables fall outside the cited edition’s scope. Confirm the jacket legend, check the drawing or supplier datasheet, and use the conductor colors to verify the intended polarity. See the IEC 60584-3 scope and RAS Thermal’s comparison of conductor colors.
What do these two wire colors indicate?
| Colors on the two conductors | Common reading | First thing to verify |
|---|---|---|
| Red and yellow | ANSI Type K. Yellow is positive. | Confirm K or KX on the cable and Type K on the channel. |
| Black and red | Ambiguous when only these colors are known. | Check whether black is a Type J extension jacket around inner white and red wires, or an actual conductor in a different scheme. |
| Black and white | IEC Type J. Black is positive. | Verify both colors are individual wires and the cable is IEC-coded. |
| Blue and white | Depends on the applicable wiring convention. | Check for a legacy pair, a third conductor, or a blue jacket surrounding a different internal pair. |
| Green and white | IEC Type K. Green is positive. | Read the jacket designation to distinguish standard extension from compensating cable. |
A color mentioned in a repair note can refer to a jacket, connector body, terminal label or internal conductor. A useful note records each item separately. For instance, “black outer jacket, white and red conductors, JX printed on jacket” provides more evidence than “black and red wire.” Old regional codes and a custom assembly built to a company drawing can produce combinations that differ from the two tables. Verify the documentation at both ends when equipment or cables came from different regions.
Type J and Type K color codes
Type J commonly uses iron on the positive leg and a copper-nickel alloy on the negative leg. Under the U.S. convention the positive insulation is white and the negative is red. Under the normal IEC extension convention the positive insulation is black and the negative is white. This means white switches from the positive side of ANSI Type J to the negative side of IEC Type J. That distinction matters when reading a replacement cable specification without seeing the physical connector.
Type K uses nickel-chromium and nickel-aluminum alloy legs. Its U.S. pair is yellow positive and red negative. The IEC pair is green positive and white negative. Type J and Type K use different voltage-temperature relationships, so use the correct input mode and the matching extension or compensating cable specified for the sensor. Replacing one pair with the other can create a plausible reading at one point and a significant error as the measurement or transition temperature changes. The NIST ITS-90 thermocouple reference provides the separate voltage-temperature functions.
Type T and Type E polarity
For Type T, the positive thermocouple leg is copper. Its insulation is blue in the common U.S. scheme and brown in the IEC extension scheme. The copper-nickel negative leg is red in ANSI/ASTM identification and white in IEC identification. A blue outer jacket on U.S. Type T extension cable can help identify the pair, but blue on its own gives you less information than a visible blue-and-red pair supported by the part number.
For Type E, the positive leg is nickel-chromium and the negative leg is a copper-nickel alloy. Both conventions use a purple or violet positive conductor in the usual color charts. The negative leg distinguishes the schemes shown here, with red for the U.S. convention and white for IEC. Where the color appearance is affected by age or lighting, use the cable label and documentation to corroborate the reading.
When replacing the measurement pair rather than identifying its colors, compare the alloy legs and extension requirements in the Type J and Type K wire guide. For platinum-based sensing circuits, the Type S wire guide explains the PtRh10 and platinum sensing pair and its separate compensating cable.
Why a three-wire sensor needs a separate wiring check
A basic thermocouple measurement uses two dissimilar conductors joined at the measuring junction. A third visible wire could be a drain connection for a cable shield, part of a different sensor design or an additional function specified by the assembly drawing. A three-lead resistance temperature detector is another possibility. Its instrument measures resistance, and the extra conductor can be used to compensate for lead resistance. Different terminal and instrument settings apply to these arrangements.
Look for a sensor designation, part number and wiring diagram before applying a thermocouple color chart to a three-wire assembly. Trace the three terminations according to the device documentation. Where the assembly specification identifies a shield or drain, connect it only as required by the instrument or system design. A quick color match alone cannot establish what the third conductor does. For miniature sensor leads and custom designs, see ultra-fine temperature-sensing leads.
Check the complete measurement circuit
Read the sensor designation and record the expected calibration type at the instrument channel. Identify the standard for each cable segment and match positive to positive and negative to negative at junctions and connectors. If a system uses a transition between two color systems, label the type and polarity explicitly on both sides. A green conductor may connect to a yellow conductor in a correctly documented Type K transition. Matching wire colors across that transition would miss the fact that the same leg uses a different color in the other system.
Verify the grade of the segment between the sensor and instrument. Thermocouple-grade wire is used in the sensing pair under the conditions specified for that material and construction. Extension and compensating cables have their own operating conditions and limits of error. A compensating alloy pair approximates the applicable thermocouple behavior over its specified range. The suffix on the cable and the supplier’s published range therefore matter when a connector or junction will operate away from normal ambient conditions.
If a channel error appears after rewiring, verify the configured type, conductor polarity, cable grade and transition locations before adjusting the instrument. Review the reference-junction configuration and follow the equipment documentation for an independent temperature or signal check. Record any changes with the cable designation. Keeping the original configuration and test conditions makes it easier to distinguish a wiring issue from a sensor, connector or instrument fault. ASTM E230/E230M describes the reference tables and categories of tolerances used for standardized thermocouples and associated wires.
How to document a cable change
When a service team replaces an extension cable, record the markings of both the removed and the new parts. Capture the active channel identifier, sensor type, wire designation, the insulation colors on each leg, and the instrument terminal labels. A record that says only “rewired to match colors” is especially hard to interpret when the old cable is IEC and the new one is ANSI. Write down which conductor went to the positive terminal so that the next technician can repeat the checks without relying on a photograph.
For equipment assembled in several plants, put the required cable identification standard in the bill of materials and use part-specific labels at the transitions. Document whether variants with a different convention are approved and, if so, which terminal mapping must be followed. A receiving check can compare the part number and legend with the approved specification before the cable is installed. This is also an opportunity to confirm that the material grade, construction and cable temperature rating shown on the supplier’s documents match the purchase requirement.
If the conductor colors are inaccessible in a molded connector, use its type markings and the equipment wiring document. A batch label or supplier record is more reliable than an assumed connection based on the housing color. When the documentation and physical markings disagree, confirm the assembly identity before treating the readings as valid.
From a color code to an OEM wire specification

For a new device design, specify the thermocouple type, intended grade, conductor size, insulation construction, required color convention and any lead identification applied at the connector. Also define the junction geometry, length, termination and the conditions where the sensor and cable will be evaluated. Identify where the sensing pair transitions to extension wire. A conductor color belongs in that specification alongside the alloy and function so that both procurement and assembly teams can identify the correct part.
MOOSEN reviews requirements for medical temperature sensors and thermocouples. Include the available space for the junction and leads, how the assembly will be routed and what instrument or connector it must mate with. If the wire size or insulation identification is still open, distinguish the dimensions that must be met from the ones your development team can review. For a new design or a change to an existing lead, use the request form below to submit a drawing for review.
Thermocouple wire color questions
Is red positive or negative on thermocouple wire?
In the common ANSI/ASTM pairs shown above, red is the negative conductor. Other wiring systems and proprietary assemblies can assign colors differently. Check which identification convention applies before using color to determine polarity.
Is a blue thermocouple always Type T?
A U.S. blue positive conductor with a red negative is consistent with Type T, as is a blue jacket on standard U.S. Type T extension cable. A blue sheath by itself has several possible meanings, including special cable identification. Confirm the printed designation.
Why do imported Type J and Type K cables have different colors?
They can follow a different regional or international identification convention even when the same thermocouple type and polarity are specified. A transition record should identify each conductor by function and show the source standard for each segment.
Should I match the connector color or the insulated wires?
Use the connector’s type and polarity markings with the cable legend and conductor identification. The connector housing color is a useful cross-check once you know which convention it follows.
Do these reference charts give the wire’s operating limits?
The charts identify common colors and polarity. Look up the operating range, tolerance class and insulation limits in the actual sensor or wire specification. A wire’s temperature capability also depends on its construction and installation.